Cat Switchgear

Switchgear and Paralleling Controls

Cat Paralleling Switchgear is the perfect complement for the control and distribution of your emergency power. Modular and Customizable, it can be designed with protection and control architecture.

Show
Configuration IP4X
Operating Temperature 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F)
Standard Widths 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A.
Technical Summary Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers.

Availability Please Call Admin

OVERVIEW

Caterpillar offers a range of integrated switchgear solutions, from standard floor standing low voltage ACB's breakers 1600A - 4000A to custom solutions, which can include multiple utility sources with multiple generator paralleling applications where complex control philosophies are employed. Caterpillar has developed a modular low voltage switchgear enclosure range which integrates controls and PLC solutions. Built around 150mm modules in 3 axis, internally the framework utilises a 25 mm grid allowing a fully configurable system. Enclosure options include form 4 separation, IP54 protection and 50 °C capabilities.

FEATURES & BENEFITS

Cat Switchgear

Independently certified to meet IEC 61439-2:2011 BS & international standard. Standard ACB breaker range 1600A - 4000A CE & EAC marked.Standard breaker fault rating 65 kA... Read more

SPECIFICATIONS FOR Cat Switchgear

Collapse All
Enclosure Rating
Configuration IP4X
Operating Temperature
Operating Temperature 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F)
Dimensions
Standard Widths 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A.
Standard Heights Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping
Standard Depths 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers
Technical Summary
Technical Summary Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers.
Application
Application LV 380…480 VAC, 50 Hz, 3-Phase.
Modes of Operation
Modes of Operation Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc.

SELECT MODELS TO COMPARE

Switchgear and Paralleling Controls

Cat Customizable Switchgear and Controls

Configuration Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc
Modes of Operation All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical power needs
Application LV and MV ( 208V - 38 kV) 50 / 60 Hz
ANSI Protective Devices Per customer specification
Switchgear and Paralleling Controls

Cat EGP Switchgear

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
Application LV and MV (208V - 38 kV)
ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51
Switchgear and Paralleling Controls

Cat XLM Switchgear

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application LV and MV ( 208V - 38 kV
ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51
Switchgear and Paralleling Controls

EMCP 4.4 Master Control Panel

Configuration Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
Modes of Operation Emergency standby, island, utility paralleling
Application LV and MV (208V - 38 kV)
ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51
Switchgear and Paralleling Controls

Engine Paralleling and Integration Control (EPIC)

Configuration Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application LV and MV (208V-27kV)
ANSI Protective Devices 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)
Switchgear and Paralleling Controls

PLC and SCADA Control Systems

Configuration IP4X
Operating Temperature 0 - 50 °C (32 - 122 °F)
Dimensions Depth 750 mm, Width 750 mm, Height 2200 mm
Application LV and MV
Switchgear and Paralleling Controls

Modular Switchgear fleXible (MSX) Range

Standard Widths 600 mm for MSX1600, MSX2000 and MSX2500; 750 mm for MSX3200, MSX4000 and MSX4000
Standard Heights Heights stated without removable plinth: 1800 mm for MSX1600, MSX2000, MSX2500, and MSX3200; 2250 mm for MSX4000 and MSX4000
Technical Summary Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers.
Standard Depths 900 mm
Switchgear and Paralleling Controls

Cat Microgrid master Controller (MMC-M)

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
Application LV and MV (208V - 38 kV)
ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51
of

How to buy

VIEW ALL
01
SEND REQUEST

Select your equipment and fill out your contact information

02
GET A QUOTE

A sales rep will send you an official quote and other related information

03
PAYMENT & DELIVERY

Payment – Lead time - Delivery

Select Up to
3 Models to Compare
Model 1
Model 2
Model 3